Koszyk

Twój koszyk jest pusty teraz.

Zrób zakupy

Diesel Generator Troubleshooting Manual: Common Faults and Self-Inspection Tips

15 lip 2025 CITYLION | power your life

Diesel Generator Troubleshooting Manual: Common Faults and Self-Inspection Tips

Estimated reading time: 6–7 minutes

Even the most reliable diesel generators may experience occasional faults, especially under heavy load or in harsh environments. Knowing how to quickly identify and resolve issues is essential to minimizing downtime and maintaining productivity.

In this article, we share a troubleshooting manual that covers the most common generator faults, their likely causes, and recommended self-inspection procedures. This guide is particularly useful for after-sales support teams and end-users performing on-site diagnostics before requesting professional service.


1. Generator Fails to Start

🔍 Possible Causes:

  • Low or dead battery

  • Insufficient fuel

  • Faulty starter motor or solenoid

  • Emergency stop engaged

  • Controller or sensor malfunction

🛠️ Inspection Tips:

  • Check battery voltage (should be 12V or 24V depending on model)

  • Confirm fuel level and fuel filter condition

  • Ensure emergency stop button is released

  • Inspect starter wiring and fuses

  • Reset the controller and check for error codes


2. Low Output Voltage or No Voltage

🔍 Possible Causes:

  • Alternator failure or AVR fault

  • Loose or damaged wiring

  • Load imbalance or overload

  • Incorrect frequency settings

🛠️ Inspection Tips:

  • Verify output voltage and frequency on control panel

  • Check AVR (Automatic Voltage Regulator) and alternator connections

  • Tighten all terminal connections

  • Reduce load and test output again

  • Inspect excitation wires and fuses


3. Engine Overheating

🔍 Possible Causes:

  • Blocked radiator or dirty coolant

  • Low coolant level

  • Faulty thermostat or fan

  • Overload conditions

🛠️ Inspection Tips:

  • Check coolant level and refill if needed

  • Clean radiator fins and ensure airflow is unobstructed

  • Inspect fan belt tension and wear

  • Monitor engine temperature via controller

  • Reduce load and observe performance


4. Unusual Noise or Vibration

🔍 Possible Causes:

  • Loose mounting bolts

  • Misalignment of generator and engine

  • Worn-out bearings or fan damage

  • Internal mechanical failure

🛠️ Inspection Tips:

  • Stop generator and inspect all mounting hardware

  • Listen for knocking, screeching, or rattling sounds

  • Check vibration dampers under base frame

  • Perform visual check for oil leaks or cracks


5. Excessive Smoke from Exhaust

Smoke Color Likely Cause Suggested Check
White Unburned fuel or coolant leak Check injectors and coolant level
Blue Burning oil Inspect piston rings and valve seals
Black Incomplete combustion or dirty air filter Clean or replace air filter; check fuel mix

6. Oil or Fuel Leaks

🔍 Common Leak Points:

  • Fuel injection pump

  • Oil filter gasket

  • Drain plug

  • Fuel hose connections

🛠️ Inspection Tips:

  • Use a clean cloth to trace leaks

  • Tighten hose clamps and pipe fittings

  • Replace damaged seals or hoses

  • Never run a generator with active leaks


7. Battery Not Charging

🔍 Possible Causes:

  • Defective alternator or voltage regulator

  • Loose battery connections

  • Worn-out battery

🛠️ Inspection Tips:

  • Measure charging voltage (should be ~13.5V–14.5V for 12V systems)

  • Clean battery terminals

  • Replace battery if over 2–3 years old or if voltage drops quickly under load


8. Control Panel Error Codes

Many modern generators use smart controllers (e.g., Deep Sea, SmartGen, ComAp) that display diagnostic codes.

🛠️ Inspection Tips:

  • Refer to user manual or contact supplier for code definitions

  • Clear faults via “Reset” after resolving underlying issue

  • Keep a log of recurring codes to identify patterns


General Preventive Maintenance Checklist

Task Frequency
Check oil and coolant Daily
Clean air filters Weekly
Test battery voltage Weekly
Inspect belts and hoses Monthly
Run generator under load Monthly

Preventive maintenance is the best way to avoid unexpected generator faults.


Conclusion

With this troubleshooting checklist, you can quickly identify and resolve many of the most common diesel generator faults before they escalate into costly repairs or downtime. Whether you're an end-user, technician, or after-sales service team, having a structured inspection routine ensures reliable generator performance in all operating conditions.


Author: Service & Support Division – [Ningde City Lion Motor Co., Ltd.]
Last updated: July 15, 2025

Powróć do blogu

Wysłaj komentarz

Uwaga, komentarz będzie opublikowany po weryfikacji